Automation Protection Relay Testing K68i , Single Phase
All-in-one design relay tester with 6.4 inches LCD display
Binary Inputs Number: 8 pairs
Binary output Number :4 pairs
With all in one design, able to test most of relays by manual or automation!
Software Features:
1. Able to test most of Relays by manual or automation: Voltage
relays, Current relays, Frequency relays,
Power relays, Impedance relays, Harmonic relays, Distance relays
etc;
2. With self housing-grounding-detecting function, the software
interface can show whether the housing
well grounding or not, effectively ensure the safety of testing.
Hardware Features:
1. All-in-one design relay tester with 6.4 inches LCD display;
2. 4 Phase AC Voltage Sauce and 3 phase AC current source can be
output together, even the Range,
Phase, Frequency can be set independently;
3. Max AC voltage can reach 300V each phase, Offer independent Aux.
DC to tested devices, 0 ~ 300
V/0.6A (Poleless and adjustable);
4. Offer different type of computer port: USB port, RJ45 port, VGA
Video Port , USB / RJ45 ports
convenient for data transfer, VGA Video Port can connect to
projector and easy for study and training;
5. Super long life Rotary encoder + Functional keyboard.
Technical Data of K68
| Voltage generators | ||
| Setting Range | 4-phase AC (L-N) | 4 x 0 ... 300V | 
| 2-phase AC (L-L) | 2x 0 ...600 V | |
| Power | 4-phase AC (L-N) | 4 x110VA, at 0 ...300 V | 
| 2-phase AC (L-L) | 2 x 220VA, at 0 ...600 V | |
| Accuracy | <0.07% reading + 0.03% range guaranteed at 0-300V <0.04% reading + 0.01% range typical at 0-300V | |
| Resolution | 1mV | |
| Current generators | ||
| Setting Range | 3-phase AC (L-N) | 3 x 0 ... 35 A | 
| 1-phase AC (3L-N) | 1 x 0 ...105 A | |
| Power | 3-phase AC (L-N) | 1x 450VA, at 0 ... 35A | 
| 1-phase AC (3L-N) | 1 x 1000VA, at 0 ...105A | |
| Accuracy | <0.14% reading + 0.06% range guaranteed at 0-35A <0.05% reading + 0.02% range typical at 0-35A | |
| Resolution | 1mA | |
| Generators, general | ||
| Frequency | Range | 0 ... 1000 Hz | 
| Accuracy / drift | Error < 0.001Hz at 10 ... 65Hz, Error < 0.01Hz at 65Hz...450Hz Error < 0.02Hz at 450Hz...1000Hz | |
| Resolution | 0.001Hz | |
| Phase | Range | - 360° ... +360° | 
| Accuracy / drift | Error < 0.2 ° | |
| Resolution | 0.1° | |
| Time | Range | 0 ... 999, 999.999s | 
| Accuracy / drift | Error<1ms | |
| DC generators | ||
| Voltage ranges | 0 ... 300V/180VA | |
| Current ranges | 0 ... 20A/300W | |
| Accuracy | Error<0.1% reading + 0.1% range guaranteed at 0…300 V; Error <0.1% reading + 0.1% range guaranteed at 0...20 A; | |
| Resolution | 1mA; 1 mV | |
| Aux DC Supply | ||
| Range | 0...300V/0.6A | |
| Binary inputs | ||
| Number | 8 pairs | |
| Compatible Voltage | 10V ... 250V DC | |
| Binary outputs | ||
| Number | 4 Pairs | |
| Capacity | 250V/3A (AC/DC) | |
| Synchronization | ||
| Synchronization mode | GPS | |
| Harmonic | ||
| Harmonic overlap times | 2 ... 9 times | |
| Power supply | ||
| Nominal input voltage | 220V±20% VAC, 1-phase | |
| Power | 1000VA | |
| Nominal frequency | 50±10% Hz | |
| Environmental conditions | ||
| Operation temperature | -5°C ... 55 °C | |
| Storage temperature | -20°C ... 75 °C | |
| Humidity range | 5% ... 90 %, non-condensing | |
| Weight | 20KG | |
| Dimensions | 460(D)×140 (W)×360 (H) mm | |
| Interface | RJ45 , USB, VGA | |
Main Series Relay Tester List:
| K68 series | K68 | 3x35A, 4x130V, 5 function modules, Ethernet, TFT LCD, WinCE | 
| K68i | 3x35A, 4x300V, 5 function modules, Ethernet, TFT LCD, WinCE | 
Major Functions:
| Items | IEEE(R) No. | 
| Overcurrent relays | 50/76 | 
| Inverse time overcurrent relays | 51 | 
| Undercurrent relays | 37 | 
| Ground fault relays | 50 | 
| Directional overcurrent relays | 67 | 
| Directional ground fault relays | 67N | 
| Overvoltage relays | 59 | 
| Undervoltage relays | 27 | 
| Directional voltage relays | 91 | 
| Directional power relays | 32 | 
| Power factor relays | 55 | 
| Distance protection equipment (phase by phase) | 21 | 
| Automatic reclosing devices | 79 | 
| Tripping relays | 94 | 
| Voltage regulating relays | |
| Overimpedance relays, Z> | |
| Underimpedance relays, Z | |
| Time-delay relays | 

|   | 