| Brand Name : | GENY |
| Model Number : | YCATS II |
| Certification : | ISO, CE |
| Price : | negotiate rates |
| Payment Terms : | T/T, L/C, D/P, T/T |
| Supply Ability : | 2 sets/ 3 months |
| Delivery Time : | 6~8weeks |
Poly Phase Energy Meter Automatic Test Pipeline Closed Link Testing Easy Expansion PC Control
This is a 3 phase automatic test lines, by a power cabinet (model: YC1893D) and 20 test stations, whereof each station equips a set of Isolated Current Transformer (ICT model: TICT-100) for operating independently. automatic systems adopts pneumatic drive and including robot arm.
Application Conditions and Requirements | |||||
| Environment | Power Requirement | Safety | |||
| Operation Temperature | Humidity | Altitude | Voltage Supply | IP Class | Conformity |
| -10°C--+40ºC | 35%--85% | <2500m | 3x220/380V±10% (or customized) 50/60Hz±2Hz | IP30 | CE conform |
| Type | YCS-103-250 | YCS-103-800 | YCS-103-1200 | YCS-203-2500 |
| Voltage | ||||
| Test voltage output(Phase-Neutral) | 3x(24V-300V)(or customized) | |||
| Power of the voltage output | Max.3x100VA | Max.3x250VA | Max.3x500VA | Max.3x1000VA |
| Resolution | Better than 0.01%of full scale value of range | |||
| Setting accuracy | Better than 0.05% at the final range value | |||
| Stability | Better than 0.005%/h(integration time 150 s) | |||
| Load regulation from 0-max.load | Better than 0.01% | |||
| Distortion factor | Better than 0.3% for linear resistance load | |||
| Harmonics | 2nd-41st free programmable | |||
| Current | ||||
| Test current output | 3x(1mA-120A/200A) | |||
| Power of the current output | Max.3x250VA | Max.3x500VA | Max.3x1000VA | Max.3x2000VA |
| Resolution | Better than 0.01% of full scale value of range | |||
| Setting accuracy | Better than 0.05%at the final range value | |||
| Stability | Better than 0.005%/h(integration time 150 s) | |||
| Load regulation from 0-max.load | Better than 0.01% | |||
| Distortion factor | Better than 0.3% for linear resistance load | |||
| Harmonics | 2nd-41st free programmable | |||
| Phase angle | ||||
| Range | 0-360° | |||
| Resolution | 0.01° | |||
| Setting accuracy | 0.1° | |||
| Frequency | ||||
| Range | 45Hz-65Hz | |||
| Resolution | 0.01Hz | |||
| Error display | ||||
| Type of error display | Red LED | |||
| Resolution of the error displays | 8 digits | |||

|