| Item Name | ETCR-5000 Best Price Handheld Three Phase AC Power Quality Analyzer | 
| Power supply | Rechargeable lithium-ion battery pack 9.6V, backup charger. | 
| Battery indicator | Battery symbol shows dump energy. When the voltage is too low,
automatic shutdown after the 1 minute. | 
| Power consumption | Current consumption of normal test 490mA, continuous working for
8h. | 
| Display mode | LCD color screen,5.6 inches | 
| Instrument dimensions | L×W×H: 240mm×170mm×68 mm. | 
| Size of clamp | 008 small sharp current clamp: 7.5mm×13mm;040 circle current clamp: 35mm×40mm;
 068 circle current clamp: 68mm×68mm;
 | 
| Number of channels | 4U/4I. | 
| Phase-to phase voltage | 1.0V~2000V. | 
| Phase-to-neutral voltage | 1.0V~1000V. | 
| Current | 008 current clamp: 10mA~10.0A; 040 current clamp: 0.10A~100A;068 current clamp: 1.0A~1000A;
 Optional current transformer: instrument input current 1mA~500mA.
 | 
| Frequency | 40Hz~70Hz. | 
| Parameters of electricity | W, VA, Var, PF, DPF, cosφ, tanφ. | 
| Energy parameters | Wh, Varh, Vah. | 
| Harmonic | Order 0~50. | 
| Total harmonic distortion | Order 0~50, each phase. | 
| Expert mode | Yes. | 
| Number of Transient records | 150 sets. | 
| Voltage flicker | Yes. | 
| Starting current mode | Yes, 100 seconds. | 
| 3 phases unbalance | Yes. | 
| Record | 300 days(simultaneous recording 20 parameters, record one point
every 5 seconds). | 
| Min/Max recorded value | Measurement of max. and min. values over a period of time. | 
| Alarm | 40 types of parameter selections, 12,800 sets alarm logs. | 
| Peak | Yes. | 
| Phasor diagram display | Automatically. | 
| Capacity of snapshots | 60. | 
| Menu language | English/Chinese. | 
| Communication | USB. | 
| Automatic switching off | When an alarm campaign is initiated or a search for transients, an
inrush current capture, or a trend recording is pending or in
progress, the device is not automatic switching off. | 
| In other test mode, 15 minutes without keystrokes, automatic
shutdown after prompt 1 minute. | 
| Backlight function | Yes, suitable for use at night and dark place. | 
| Weight | Host: 1.6kg (with battery). | 
| 008 small sharp current clamp: 170g×4; | 
| 040 circle current clamp: 190g×4; | 
| 068 circle current clamp: 510g×4; | 
| Test wires and power adapter: 900g; | 
| Total weight: about 10.5kg (with packaging). | 
| Length of voltage test wire | 3m. | 
| Length of current sensor wire | 2m. | 
| Working environment | -10°C~40°C; below 80%Rh. | 
| Storage environment | -10°C~60°C; below 70%Rh. | 
| Input impedance | Input impedance of test voltage: 1MΩ. | 
| Withstand voltage | Withstand 3700V/50Hz sinusoidal AC voltage for 1 minute between
instrument wiring and shell. | 
| Insulation | Between instrument wiring and shell ≥10MΩ. | 
| Structure | Double insulation, with insulation vibration-proof sheath. | 
| Safely rules | IEC 61010 1000V Cat III / 600V CAT IV, IEC61010-031, IEC61326,
Pollution degree: 2. | 
| Packing information | 400× 270×270(mm) (L ×W ×H), 8Kg |