Sign In | Join Free | My burrillandco.com
Home > Power Cables >

Type SHD-GC Special Cables EPR Insulated And CPE / TPU Jacket Heat Resistant

    Buy cheap Type SHD-GC Special Cables EPR Insulated And CPE / TPU Jacket Heat Resistant from wholesalers
     
    Buy cheap Type SHD-GC Special Cables EPR Insulated And CPE / TPU Jacket Heat Resistant from wholesalers
    • Buy cheap Type SHD-GC Special Cables EPR Insulated And CPE / TPU Jacket Heat Resistant from wholesalers
    • Buy cheap Type SHD-GC Special Cables EPR Insulated And CPE / TPU Jacket Heat Resistant from wholesalers

    Type SHD-GC Special Cables EPR Insulated And CPE / TPU Jacket Heat Resistant

    Ask Lasest Price
    Brand Name : CN CABLE
    Model Number : SHD-GC
    Certification : CE
    Payment Terms : L/C, T/T
    Delivery Time : 30days after payment
    • Product Details
    • Company Profile

    Type SHD-GC Special Cables EPR Insulated And CPE / TPU Jacket Heat Resistant

    Type SHD-GC Special Cables EPR Insulated And CPE / TPU Jacket Heat Resistant


    APPLICATION
    Trailing cable on ac mining equipment where service conditions are severe and maximum safety is mandatory; such as
    power shovels and drag lines in open-pit mines, quarries, gantry cranes and slag reclaiming.
    Used for high voltage distribution in underground mines where frequent relocation is necessary or where extra
    flexibility and toughness is desired.
    Meets all requirements of ICEA S-75-381.
    CHARACTERISTIC
    Excellent flexibility
    Highly ozone, sun, weather and flame resistant
    Excellent impact and abrasion resistant
    Rated and flexible at -500C
    Oil and heat resistant



    1. Phase, Grounding Conductors, Ground check conductors: Soft or annealed tinned coated copper
    conductor, rope lay flexible stranding per ASTM B172
    2. Conductor Shield: A helically applied semiconducting tape.
    3. Insulation: High quality, heat, moisture, ozone and thermosetting ethylene propylene rubber (EPR)
    meeting ICEA.
    4. Insulation Shield: An overlapped semiconducting tape shall be applied over the insulation.
    5. Metallic Component: A composite fiber-copper braid shield, tinned coated copper wires, Coverage
    minimum 60 ,with colored fibers for phase identification (black, white, red).
    6. Assembly: Phase, ground check and grounding conductors cabled together with hygroscopic fillers and a
    binder tape.
    7. Ground Check: Polypropylene insulation yellow colored for identification.
    8. Jacket(CPE): Heavy duty or extra heavy duty chlorinated polyethylene (CPE) compound, applied in one
    layer over a fibrous reinforcement layer, Black or other colors can be provided.
    8. Jacket(TPU): Extra heavy duty, high torsion resistant, integral-filled, thermoplastic Polyurethane jacket,
    Black or other colors can be provided.


    Technical Data

    SHD-GC 2 kV
    Selection data
    Power
    conductor size
    Power conductor
    stranding
    Nominal
    thickness of
    insulation
    Jacket
    thickness
    Grounding conductorApproximate overall
    diameter
    Ampacity
    40°Cambient
    temperature
    SizeStranding
    AWG or MCMInchesInchesAWGInchesA
    61337x190.0700.15510497x71.2693
    42597x370.0700.15581337x191.36122
    22597x370.0700.17061337x191.55159
    12597x370.0800.17051337x191.71184
    1/026619x140.0800.19042597x371.81211
    2/034219x180.0800.20532597x391.94243
    3/041819x220.0800.20522597x372.07279
    4/053219x280.0800.22012597x372.24321
    25062719x330.0950.2201/026619x142.44355
    30074037x200.0950.2351/026619x142.70395
    35088837x240.0950.2352/034219x182.73435
    500122137x330.0950.2654/053219x283.10536

    SHD-GC 5 kV
    Selection data
    Power
    conductor size
    Power conductor
    stranding
    Nominal
    thickness of
    insulation
    Jacket
    thickness
    Grounding conductorApproximate overall
    diameter
    Ampacity
    40°Cambient
    temperature
    SizeStranding
    AWG or MCMInchesInchesAWGInchesA
    61337x190.1100.18510497x71.5193
    42597x370.1100.18581337x191.60122
    22597x370.1100.20561337x191.79159
    12597x370.1100.20551337x191.88184
    1/026619x140.1100.22042597x371.98211
    2/034219x180.1100.22032597x372.12243
    3/041819x220.1100.23522597x372.26279
    4/053219x280.1100.23512597x372.51321
    25062719x330.1200.2501/026619x142.57355
    35088837x240.1200.2652/034219x182.83435
    500122137x330.1200.2804/053219x283.18536

    SHD-GC 8 kV
    Selection data
    Power
    conductor size
    Power conductor
    stranding
    Nominal
    thickness of
    insulation
    Jacket
    thickness
    Grounding conductorApproximate overall
    diameter
    Ampacity
    40°Cambient
    temperature
    SizeStranding
    AWG or MCMInchesInchesAWGInchesA
    42597x370.1500.20581337x191.9393
    22597x370.1500.22061337x192.02122
    12597x370.1500.22051337x192.10159
    1/026619x140.1500.22042597x372.21184
    2/034219x180.1500.23532597x372.34211
    3/041819x220.1500.25022597x374.49243
    4/053219x280.1500.25012597x372.63279
    25062719x330.1500.2501/026619x142.75321
    35088837x240.1500.2802/034219x183.05355
    500122137x330.1500.2954/053219x283.39435

    SHD-GC 15 kV
    Selection data
    Power
    conductor size
    Power conductor
    stranding
    Nominal
    thickness of
    insulation
    Jacket
    thickness
    Grounding conductorApproximate overall
    diameter
    Ampacity
    40°Cambient
    temperature
    SizeStranding
    AWG or MCMInchesInchesAWGInchesA
    22597x370.2100.23561337x192.31164
    12597x370.2100.23551337x192.40187
    1/026619x140.2100.25042597x372.52215
    2/034219x180.2100.25032597x372.60246
    3/041819x220.2100.26522597x372.79283
    4/053219x280.2100.26512597x372.90325
    250*62719x330.2100.2651/026619x143.05355
    350*88837x240.2100.2802/034219x183.31435
    500*122137x330.2100.2954/053219x283.72536

    SHD-GC 25 kV
    Selection data
    Power
    conductor size
    Power conductor
    stranding
    Nominal
    thickness of
    insulation
    Jacket
    thickness
    Grounding conductorApproximate overall
    diameter
    Ampacity
    40°Cambient
    temperature
    SizeStranding
    AWG or MCMInchesInchesAWGInchesA
    22597x370.2950.23561337x192.55178
    12597x370.2950.26551337x192.86191
    1/026619x140.2950.26542597x372.91218
    2/034219x180.2950.28032597x373.06249
    3/041819X220.2950.28022597x373.19286
    4/053219x280.2950.29512597x373.34327
    250*62719x330.2950.2951/026619x143.43360
    350*88837x240.2950.2952/034219x183.66435

    Quality Type SHD-GC Special Cables EPR Insulated And CPE / TPU Jacket Heat Resistant for sale
    • Haven't found right suppliers
    • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
    • And this service is free of charge.
    • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
    Submit Buying Request
    Send your message to this supplier
    *From:
    Your email address is incorrect!
    *Subject:
    Your subject must be between 10-255 characters!
    *Message:
    For the best results, we recommend including the following details:
    • --Self introduction
    • --Required specifications
    • --Inquire about price/MOQ
    Your message must be between 20-3,000
    Yes! I would like your verified suppliers matching service!
    Send your message to this supplier
     
    *From:
    *To: CN Cable Group Co., Ltd.
    *Subject:
    *Message:
    Characters Remaining: (0/3000)
     
    Explore more Special Cables products from this supplier
    Find Similar Products By Category:
    Inquiry Cart 0