The TBC-SYHA/SYHWA series current sensor is a two-closed loop device based on the measuring principle of the hall effect, with a galvanic isolation between primary and secondary circuit. It has strong anti-jamming ability and provides accurate electronic measurement of DC, AC or pulsed currents.
| Electrical data(Ta=25℃±5℃) | 
| Type Parameter | TBC05SYHA /SYHWA | TBC7.5SYHA /SYHWA | TBC10SYHA /SYHWA | TBC15SYHA /SYHWA | TBC20SYHA /SYHWA | TBC25SYHA /SYHWA | TBC30SYHA /SYHWA | TBC50 SYHA | Unit | 
| Rated input(Ipn) | 5 | 7.5 | 10 | 15 | 20 | 25 | 30 | 50 | A | 
| Measuringrange(Ip) | 15 | 22.5 | 30 | 45 | 60 | 75 | 90 | 125 | A | 
| Size of input pins | ø 0.6 | ø 0.8 | ø 0.8 | ø 1.0 | ø 1.4 | ø 1.4 | ø 1.6 | □1.6 ×1.5×2 | mm | 
| Turns ratio(Np/Ns) | 5:1250 | 3:1125 | 3:1500 | 2:1500 | 1:1000 | 1:1250 | 1:1500 | 1:2500 | |
| Measuring resistance range | 100-300 | Ω | |||||||
| Rated output (Isn) | @ Ip=±Ipn ±20±0.5% | mA | |||||||
| Supply voltage | ±15±5% | V | |||||||
| Power consumption | 20+IpX(Np/Ns) | mA | |||||||
| Zero current | @ Ip=0 ≤±0.2 | mA | |||||||
| Offset drift | @ -40~+85℃ ≤±0.5 | mA | |||||||
| Linearity | @ Ip=0-±Ipn ≤0.1 | %FS | |||||||
| Response time | @ Ip=Ipn, 50 A/µS ,10%-90% <1.0 | μS | |||||||
| Galvanic isolation | @ 50HZ,AC,1min 5.0 | KV | |||||||
| Applications | 
Variable speed drives
Welding machine
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Electrochemical
| Mechanical dimension(for reference only) | 

Remarks:
1. All dimensions are in mm.
2. Secondary pin size and tolerance: width:0.5±0.1mm;thickness:0.25±0.05mm
3. General tolerance ±1mm.
| Directions for use | 
When the current will be measured goes through the primary pin of a sensor, the current will be measured at
the output end. (Note: The false wiring may result in the damage of the sensor).
Custom design in the different rated input current and the output current are available.
Standards
UL94-V0.
EN60947-1:2004
IEC60950-1:2001
EN50178:1998
SJ 20790-2000
| General date | 
| Value | Unit | Symbol | |
| Operating temperature | -40 to +85 | ºC | TA | 
| Storage temperature | -40 to +125 | ºC | TS | 
| Mass(approx) | 11 | g | M | 
| Characteristics chart | 
Pulse current signal response characteristic Effects of impulse noise

|   | 
 
                                 
                                 
                                 
                                