    Brand Name : Chengtiantai
    Certification : CE, ISO, IEC
    Price : On Request
    Payment Terms : L/C, T/T
    Supply Ability : 18,000 m per month
    Delivery Time : 7/15 working days
    • Product Details
    • Company Profile

    Screened Single Core Medium Voltage Power Cables PVC Sheathed N2XSY


    N2XSY Medium Voltage Power Cable single core 6/10 kV, 12/20 kV, 18/30 kV


    XLPE Insulated, Copper conductor, singe core, screened, PVC sheathed


    The singe core cables are designed for distribution of electrical power with nominal voltage Uo/U ranging from 6/10 KV to 18/30KV and frequency 50Hz. They are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations.


    CONSTRUCTION:

    1. CONDUCTOR

    – Bare copper class 2 to IEC 60228, round, multiwire stranded and compact

    2. CONDUCTOR SCREEN

    – Inner semi-conducting coating

    3. INSULATION

    – Core insulation of cross-linked polyethylene (XLPE)

    4. INSULATION SCREEN

    – Outer conductive layer extruded and per-manently welded with the core insulation

    Semi-conducting type
    – Over the outer semi-conducting layer, a semiconducting tape must be used.

    5. METAL SCREEN

    – Annealed copper tapes with a minimum thickness of 0,1 mm.

    Separator
    – Over the screen as well as under outer sheath, a separating layer must be used (e. g. taping).

    6. SHEATH

    – Outer sheath of PVC compound

    TECHNICAL DATA

    Temperature range
    – during installation up to -5°C

    Operating temperature
    – max. +90°C

    Short circuit temperature
    +250°C (short circuit duration max. 5 s)

    Minimum bending radius
    – 20 x cable Ø
    Breaking strength: min. 200%
    Tensile strength: min. 12,5 N/mm2

    Nominal voltage
    – U0/U 6/10 kV, 12/20 kV, 18/30 kV

    Operating voltage, 50 Hz
    – for 6/10 kV = max. 12 kV
    – for 12/20 kV = max. 24 kV
    – for 18/30 kV = max. 36 kV

    Test voltage(V/5 min)
    – for 6/10 kV = 21 kV
    – for 12/20 kV = 42 kV
    – for 18/30 kV = 63 kV


    6/10 kV XLPE Insulated, Copper conductor, single core, screened, PVC sheathed


    No.cores x
    cross-sec.
    Operation
    voltage
    max.
    Nominal
    voltage
    U0/U
    Insulation
    thickness
    Sheath
    thickness
    Nominal
    value
    Outer Ø
    approx.
    weight
    approx.
    Current ratings in air 30℃Current ratings buried 20℃maximum DC resistance at 20℃
    mm²kVkVmmmmmmkg / kmAAΩ/km
    1 x 35 rm126/ 103.41.620.66872051900.52
    1 x 50 rm126/ 103.41.7228552452250.39
    1 x 70 rm126/ 103.41.723.610863052750.27
    1 x 95 rm126/ 103.41.825.513513703300.19
    1 x 120 rm126/ 103.41.826.916224303750.15
    1 x 150 rm126/ 103.41.928.619324904250.12
    1 x 185 rm126/ 103.41.930.322995604800.1
    1 x 240 rm126/ 103.42.032.728646655550.08
    1 x 300 rm126/ 103.42.135.334597656300.06
    1 x 400 rm126/ 103.42.238.645548907250.05
    1 x 500 rm126/ 103.42.342.2557410308250.04
    1 x 630 rm126/ 103.42.445.9686711909400.03

    12/20 kV XLPE Insulated, Copper conductor, single core, screened, PVC sheathed


    No.cores x
    cross-sec.
    Operation
    voltage
    max.
    Nominal
    voltage
    U0/U
    Insulation
    thickness
    Sheath
    thickness
    Nominal
    value
    Outer Ø
    approx.
    weight
    approx.
    Current ratings in air 30℃Current ratings buried 20℃maximum DC resistance at 20℃
    mm²kVkVmmmmmmkg / kmAAΩ/km
    1 x 35 rm2412/ 205.51.824.98602051900.52
    1 x 50 rm2412/ 205.51.826.411382452250.39
    1 x 70 rm2412/ 205.51.928.112813052750.27
    1 x 95 rm2412/ 205.51.929.915703703300.19
    1 x 120 rm2412/ 205.5231.318394303750.15
    1 x 150 rm2412/ 205.5233.121744904250.12
    1 x 185 rm2412/ 205.52.134.725405604800.1
    1 x 240 rm2412/ 205.52.237.131206655550.08
    1 x 300 rm2412/ 205.52.239.537467656300.06
    1 x 400 rm2412/ 205.52.344.148638907250.05
    1 x 500 rm2412/ 205.52.447.6590510308250.04
    1 x 630 rm2412/ 205.52.551.3722011909400.03

    18/30 kV XLPE Insulated, Copper conductor, single core, screened, PVC sheathed


    No.cores x
    cross-sec.
    Operation
    voltage
    max.
    Nominal
    voltage
    U0/U
    Insulation
    thickness
    Sheath
    thickness
    Nominal
    value
    Outer Ø
    approx.
    weight
    approx.
    Current ratings in air 30℃Current ratings buried 20℃maximum DC resistance at 20℃
    mm²kVkVmmmmmmkg / kmAAΩ/km
    1 x 50 rm3618/ 308232.613632452250.39
    1 x 70 rm3618/ 308234.316143052750.27
    1 x 95 rm3618/ 3082.136.119193703300.19
    1 x 120 rm3618/ 3082.137.522034303750.15
    1 x 150 rm3618/ 3082.239.325564904250.12
    1 x 185 rm3618/ 3082.240.929345604800.1
    1 x 240 rm3618/ 3082.343.335406655550.08
    1 x 300 rm3618/ 3082.445.741917656300.06
    1 x 400 rm3618/ 3082.549.152468907250.05
    1 x 500 rm3618/ 3082.654.6656110308250.04
    1 x 630 rm3618/ 3082.758.4790611909400.03


    *Dimensions and specifications may be changed without prior notice.


    MEDIUM VOLTAGE CABLE TESTING


    Routine tests:Sample tests:Type tests:
    These non-destructive tests are normally carried out on all lengths manufactured.
    - Conductor resistivity
    - Spark test on oversheath
    - Voltage tests on sheath
    - D.C. voltage test on oversheath
    These potentially destructive tests are normally carried out on every production run.
    - Examination of conductor and dimensions
    - Hot set test for XLPE insulation
    - Insulation and oversheath thickness
    - Four hour voltage test
    These destructive tests are normally carried out in addition to the above tests on commencement of a particular cable supply to validate its design.
    - Electrical type tests including bending and heat cycle
    - Non-electrical type tests including mechanical properties after ageing and tests under fire conditions.

    PACKING AND SHIPPING


    Packing: steel wooden drum, other as required ; standard delivery length is 300 m



    cable drum data


    D1=Flange Diameter(mm)W=Useful Width (mm)D2=Barrel Diameter(mm)Approx empty
    weight (kg)
    number per 20 feet container
    1250750600105 kg28

    Our production in numbers


    ● Cable production started 1983
    35 years of cable manufacturing experience

    ● Sales in 2016 about 500 million USD

    100,000 m2 Production area
    350 Will-trained employees
    ● Exported more than 22 countries
    2 Manufacturing plant
    1 R&D Center

    200 Sets Of Testing Equipment

    100 Testing Items
    8 workshop
    40 wire drawing machines
    10 bunching machines
    28 Extruder system
    42 stranding machines
    10 Braiding machines

    Shenzhen chengtiantai cable operates certified management systems compliant with:
    CertificatInformation
    ISO 9001:2008
    Quality management systems

    Certificat ISO 9001:2008
    - Shenzhen chengtiantai cable industry development Co.Ltd. ;
    Certified through Guangdong quality Testing CTC Certification Co.Ltd.;
    Valid until 13 January 2019
    ISO 14001:2004
    Environmental management systems

    Certificat ISO 14001:2004

    - Shenzhen chengtiantai cable industry development Co.Ltd. ;

    Certified through Guangdong quality Testing CTC Certification Co.Ltd.;

    Valid until 13 January 2019

    OHSAS 18001:2007
    Assessment specification for occupational health & safety management systemsenvironmental management systems
    Certificat OHSAS 18001:2007
    - Shenzhen chengtiantai cable industry development Co.Ltd. ;
    Certified through Guangdong quality Testing CTC Certification Co.Ltd.;
    Valid until 13 January 2019

    Manufacturing Process Of Medium Voltage Power Cable

    1. copper rod2. wire drawing3. wire stranding
    4.Triple Extrusion Insulation5.Screening Process6. outer covering Process
    7. Sheath Marking8. Packing9. Partial discharge Inspection

    Some great shot on our manufacturing plant


    Located in: Chengtiantai Industrial Park, Guangming New District, Shen zhen P. R. China 518106

    Customer services:


    RECOMMENDED ORDERING PARAMETERS

    CONTACT

    For prompt quotation / supplies please make sure your inquiries and your orders are
    securing the following data :

    1 - International or Special Standard. (Alternatively, the precise usage of the cable.)
    2 - Rated voltage.
    3 - Copper or Aluminium conductors.
    4 - Size of each conductor.
    5 - Insulation material : XLPE or others.
    6 - Number and identification of conductors.
    7 - Other requirements.
    8 - Packing.
    9 - Required delivery time.
    10 - Required validity.

    If this all seems a litle too technical for you, then why not get in touch with us.


    We look forward to assisting you in identifying the best products for your specific application and to answer any questions you might have.


    Tel:+86 755 6114 5028
    Fax:+86 755 61137976
    E-mail : cttcable@hotmail.com
    Head office:chengtiantai Industrial Park, Lisonglang community, Gongming office, Guangming district, Shenzhen P.R. China 518106


    WARRANTY


    For a period commencing on the date shipped the Goods to Buyer and continuing for a period of 12 months thereafter.

    Quality Screened Single Core Medium Voltage Power Cables PVC Sheathed N2XSY for sale
    • Haven't found right suppliers
    • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
    • And this service is free of charge.
    • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
    Submit Buying Request
    Send your message to this supplier
    *From:
    Your email address is incorrect!
    *Subject:
    Your subject must be between 10-255 characters!
    *Message:
    For the best results, we recommend including the following details:
    • --Self introduction
    • --Required specifications
    • --Inquire about price/MOQ
    Your message must be between 20-3,000
    Yes! I would like your verified suppliers matching service!
    Send your message to this supplier
     
    *From:
    *To: Shenzhen Chengtiantai Cable Industry Development Co.,Ltd
    *Subject:
    *Message:
    Characters Remaining: (0/3000)
     
    Explore more Medium Voltage Power Cables products from this supplier
    Find Similar Products By Category:
    Inquiry Cart 0