CNG310 Series Low Frequency Online UPS 10-100KVA
Snapshot:
Model:CNG310 10-100KVA(3Ph/1Ph)
Nominal Input Voltage: 380/400/415VAC
Output Power Factor:0.8
Technical parameter of CNG310 series:
| Model power | CNG310 10KVA | |||||||||
| 10KVA | 15KVA | 20KVA | 30KVA | 40KVA | 60KVA | 80KVA | 100KVA | |||
| Capacity | 8KW | 12 KW | 16 KW | 24 KW | 32 KW | 48 KW | 64 KW | 80 KW | ||
| Input | ||||||||||
| Rated Voltage | 80-300 Vac three-phase | |||||||||
| Voltage Range | ±20% | |||||||||
| Frequency Range | 45-65Hz | |||||||||
| Power Factor | >0.92with harmonic filter | |||||||||
| Current Harmonic Distortion | <5%with harmonic filter | |||||||||
| Soft Start | 0-100% in10" | |||||||||
| Bypass Input | ||||||||||
| Rated Voltage | 230Vac single-phase | |||||||||
| Permitted Voltage Range | ±15%(selectable from ±10% to ±25% from front panel) | |||||||||
| Rated Frequency | 50/60Hz | |||||||||
| Permitted Frequency Range | ±2%(selectable from ±1% to ±5% from front panel) | |||||||||
| Standard Features | BackFeed protection; split bypass line | |||||||||
| Batteries | ||||||||||
| Type | Maintenance-free lead-acid VRLA AGM / GEL;NICd | |||||||||
| Battery Voltage | 384VDC | |||||||||
| Maximum Recharge Current(A) | 0.2 X C10 | |||||||||
| AC Ripple Voltage | <1% | |||||||||
| Inverter Output | ||||||||||
| Number of Phases | 1 | |||||||||
| Rated Voltage(V) | 48Vac single-phase | |||||||||
| Regulation of the Output Voltage | 48Vac phase/neutral(from control panel) | |||||||||
| Crest Factor(Ipeak/Irms) | 3:1 | |||||||||
| Static Stability | ±1% | |||||||||
| Dynamic Stability | ±5% | |||||||||
| Frequency | 50/60Hz configurable | |||||||||
| Overload | 110% 125% 150% of the rated current for 5h/10'/1' | |||||||||
| Frequency Stability | ±0.05% on mains failure | |||||||||
| Remote Signaling | Volt free contacts | |||||||||
| Remote Controls | EPO and Bypass | |||||||||
| Communication | RS232 + remote contacts | |||||||||
| Operation Temperature | 0ºC/ + 40ºC | |||||||||
| Relative Humidity | <95% non condensing | |||||||||
| Color | Light gray (RAL 7035) | |||||||||
| Noise | 54dBA at 1m | 60dBA at 1m | 65dBA at 1m | |||||||
| Protection Degree | IP20 | |||||||||
| Efficiency Smart Mode | up to 98% | |||||||||
| Compliance | Safety:EN 62040-1-1(Directive 2006/95/EC); EMC:6200-2(Directive
2004/108/EC) | |||||||||
Application:
Servers,
Local area Network(LAN),
Data centers,
Telecommunications,
Electro-medical equipment
Maximum battery care:
Battery deep discharge protection;
Temperature compensating charger;
Built-in automatic and manual battery test feature.
High reliability:
Extremely high short-circuit current to ensure compatibility with
the most difficult transformer applications (lighting,drives and
industrial processes) and an isolation transformer on the inverter
output;
Full microprocessor control with no-break static and manual
bypasses;
IGBT technology.
Other characteristics:
Suitable for powering ICT and Industrial loads;
High level diagnostics: event log with 128 messages,
states,measurements and alarms - available from the built-in LCD
with several languages;
Back feed protection:
To avoid energy feeding back into the mains supply cause a fault
occur.
Maximum reliability and availability:
Connect up to 6 units in parallel or N+1 redundancy, even of
different power ratings.The UPS continue to work in parallel even
if one of the interconnecting communication cables is disconnected
(CLOOSED LOOP).
Low consumption level:
CNG310 can achieve efficiencies >98% thanks to selectable
Economy Mode which can be used in stable electrical environments to
provide power supply continuity when the mains fail.
Advance communication:
Compatible with TeleNetGuard for remote maintenance;
Watch & Save 3000 monitoring and shut-down software included, with
SNMP agent, for Windows 2008, Vista,2003, XP; Mac OS X,Linux,
Novell and most popular Unix operating systems;
The UPS is supplied with a cable for direct connection to the
PC(Plug and Play);
RS232 double Serial port;Installation slot for an Emergency Power
Off (EPO) interface to allow the UPS to be switched off remotely in
an emergency;
Generator interface: enables desynchronisation of the UPS output
from a generator supply which may be subject to phase and frequency
variations. The interface also enables more economic use of the
battery charge.
Expandability:
The units can be connected in parallel up to 8 units to increase
power availability or redundancy. The single module or the system
can be expanded any time to suit power requirements without
influencing the initial investment.
|