The AI825 Analog Input Module has 4 individually galvanic isolated, bipolar current/voltage inputs. Each channel can be either a voltage or current input.
The module has a direct current input that withstand up to 6.3 V and a over voltage protected current input that withstand up to +30 V d.c. The current is limited by a PTC resistor.
Power to the input stages is converted from the 24 V on the ModuleBus.
General info
| Type | Analog Input | 
| Signal specification | -20..+20 mA, 0(4)..20 mA, -10..+10 V, 0(2)..10V | 
| Article number | 3BSE036456R1 | 
| Number of channels | 4 | 
| HART | No | 
| SOE | No | 
| Redundancy | No | 
| High integrity | No | 
| Intrinsic safety | No | 
| Mechanics | S800 | 
Detailed data
| Resolution | 14 bit plus sign | 
| Input impedance | 10 MΩ (voltage input) | 
| Isolation | Individually isolated, channel-to-channel and to circuit common | 
| Under/over range | ± 15% | 
| Error | Max. 0.1% | 
| Temperature drift | Max. 47 ppm/°C (0..10V), Max. 34 ppm/°C (±10V), Max. 78 ppm/°C (0..20mA), Max. 57 ppm/°C (±20mA) | 
| Input filter (rise time 0-90%) | 115 ms (voltage input), 130 ms (current input) | 
| Update cycle time | < 10ms | 
| Maximum field cable length | 600 meters (656 yards) | 
| CMRR, 50Hz, 60Hz | 120 dB | 
| NMRR, 50Hz, 60Hz | > 40 dB at 50 Hz, >55 dB at 60 Hz | 
| Rated insulation voltage | 250 V | 
| Dielectric test voltage | 1900 V d.c. ch-ch, 3250 V d.c. ch-ground/system, | 
| Power dissipation | Typ. 2.5 W, Max. 3.2 W | 
| Current consumption +5 V Modulebus | Typ. 70 mA, Max. 100 mA | 
| Current consumption +24 V Modulebus | Typ. 90 mA, Max. 110 mA | 
| Current consumption +24 V external | 0 | 
Diagnostics
| Front LED’s | F(ault), R(un), W(arning) | 
| Supervision | Internal Power Supply | 
| Status indication of supervision | Module Error, Module Warning, Channel error | 
Environment and certification
| CE mark | Yes | 
| Electrical safety | IEC 61131-2, UL 508 | 
| Hazardous Location | - | 
| Marine certification | - | 
| Protection rating | IP20 according to IEC 60529 | 
| Corrosive atmosphere ISA-S71.04 | G3 | 
| Climatic operating conditions | 0 to +55 °C (Storage -25 to +70 °C), RH=5 to 95 % no condensation, IEC/EN 61131-2 | 
| Pollution degree | Degree 2, IEC 60664-1 | 
| Mechanical operating conditions | IEC/EN 61131-2 | 
| EMC | EN 61000-6-4, EN 61000-6-2 | 
| Overvoltage categories | IEC/EN 60664-1, EN 50178 | 
| Equipment class | Class I according to IEC 61140; (earth protected) | 
| Max ambient temperature | 55 °C (131 °F), for vertical mounting in compact MTU 40 °C (104 °F) | 
| RoHS compliance | EN 50581:2012 | 
| WEEE compliance | DIRECTIVE/2012/19/EU | 
|   | 