| Sign In | Join Free | My burrillandco.com | 
 | 
| Ask Lasest Price | |
| Brand Name : | P+F | 
| Model Number : | NJ5-18GK-N | 
| Certification : | CE | 
| Price : | negotiable | 
| Payment Terms : | T/T | 
| Supply Ability : | 100pcs per month | 
| Delivery Time : | on request | 
Extended temperature range, Switching function: Normally closed (NC), Output type: NAMUR, Installation: flush, Output type: 2-wire, Thread mold: M18, Construction type: Cylindrical, thread, Series: Cylindrical type, Safety Integrity Level (SIL): SIL 2, Type of voltage: DC, Equipment protection level Ga: IECEx PTB 11.0037X, Equipment protection level Gb: IECEx PTB 11.0037X, Equipment protection level Da: IECEx PTB 11.0037X, Equipment protection level Mb: IECEx PTB 11.0037X
Technical Data
| General specifications | ||
|---|---|---|
| Switching function | Normally closed (NC) | |
| Output type | NAMUR | |
| Rated operating distance | 5 mm | |
| Installation | flush | |
| Assured operating distance | 0 ... 4.05 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.3 | |
| Reduction factor r304 | 0.85 | |
| Output type | 2-wire | |
| Nominal ratings | ||
| Nominal voltage | 8.2 V (Ri approx. 1 kΩ) | |
| Switching frequency | 0 ... 500 Hz | |
| Hysteresis | 1 ... 10 typ. 5 % | |
| Current consumption | ||
| Measuring plate not detected | min. 3 mA | |
| Measuring plate detected | ≤ 1 mA | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| MTTFd | 4566 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Compliance with standards and directives | ||
| Standard conformity | ||
| NAMUR | EN 60947-5-6:2000 | |
| Standards | EN 60947-5-2:2007 | |
| Approvals and certificates | ||
| IECEx approval | ||
| Equipment protection level Gb | IECEx PTB 11.0037X | |
| Equipment protection level Da | IECEx PTB 11.0037X | |
| Equipment protection level Mb | IECEx PTB 11.0037X | |
| ATEX approval | ||
| Equipment protection level Gb | PTB 00 ATEX 2048 X | |
| Equipment protection level Da | PTB 00 ATEX 2048 X | |
| UL approval | cULus Listed, General Purpose | |
| CCC approval | ||
| Hazardous Location | 2020322315002255 | |
| NEPSI approval | ||
| NEPSI certificate | GYJ16.1393X | |
| CML approval | on request | |
| ANZEx | 18.3018X | |
| KCC approval | ||
| Hazardous Location | 19-AV4BO-0227 | |
| Marine approval | DNVGL TAA00001A5 | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) | |
| Mechanical specifications | ||
| Connection type | cable | |
| Housing material | PBT/PPS | |
| Sensing face | PBT | |
| Degree of protection | IP66 / IP68 | |
| Cable | ||
| Cable diameter | 6 mm ± 0.2 mm | |
| Bending radius | > 10 x cable diameter | |
| Material | PVC | |
| Core cross section | 0.75 mm2 | |
| Length | 2 m | |
| Dimensions | ||
| Length | 39 mm | |
| Diameter | 18 mm | |
| General information | ||
| Use in the hazardous area | see instruction manuals | |
Related Models:
| KCD2-SCD-EX1 | KFU8-UFT | 
| KCD2-STC-EX1.20 | K-HM26-2M-261533 | 
| KFD2-SR2-Ex1.W.LB | NBB15-U1-E2 | 
| KFD2-SR2-2.W.SM | NBB1,5-5GM25-E2 | 
| KFD2-SR2-Ex2.W.SM | NBB1,5-5GM25-E2-V3 | 
| KFD2-SR2-Ex2.2S | NBB1,5-F79-E0 | 
| KFD2-SR2-2.2S | NBB1,5-F79-E2 | 
| KFA6-DWB-EX1.D | NBB15-U1-Z2 | 
| KFA6-SR2-Ex2.W | NBB5-18GM50-E2-V1 | 
| KFA6-SR-2.3L.FA | NBB15-30GM30-E2-V1 | 
| KFA6-ER-1.5 | NBB15-30GM50-A2-V1 | 
| NBB15-30GM50-E2 | |
| KFA6-ER-1.W.LB | NBB15-30GM50-E2-M | 
| KFA6-ER-2.W.LB | NBB15-30GM50-E2-V1 | 
| NBB15-30GM50-E2-V1-M | |
| KFA6-SR-2.3L.FA | NBB8-18GM30-E2 | 
| KFA6-STR-1.24.4 | NBB8-18GM30-E2-V1 | 
| KFD0-CS-Ex1.50P | NBB8-18GM60-A2-V1 | 
| KFD2-SH-Ex1.T.OP | NJ4-12GK-SN | 
| KFD2-SL2-EX2.B | NJ5-18GK-N | 
| KFD2-SR2-EX1.W | NJ5-18GK-N-150 | 
| KFD2-SR2-Ex2.W | NJ5-18GM-N | 
| KFD2-STC5-1.2O | NJ8-18GK-N | 
| KFD2-STC5-Ex1 | RD0-FB-EX4 | 
| KFD2-STC5-Ex1.H | RD0-TI-Ex8.FF.* | 
| HIC2031 | Z787.F | 



|   | 
| Company Info. | 
| SC Automation Limited | 
| Verified Supplier | 
| View Contact Details | 
| Product List |